TS-20: DHW circulator not running

Check fuse on line voltage PC board. Is the fuse blown?

#B5

Does the display show “Standby”?

#B9

Does the display show “Domestic Hot Water”?

Yes
#B13

Go to Boiler not responding on a demand

Go
#B18

Replace the fuse with a 6.3 Amp Slow Blow Fuse.

#B23

Check 120Vac on the Line Voltage PC Boad on terminals P3-10 to the input “N”terminal. Is there 120Vac?

#B31

Check input 120Vac to the Line voltage PC board on L & N. Is there 120Vac input?

Yes
#B38

Press the “Status” button. IS the Supply Temperature and the Setpoint temperature close to the same temperature or the Supply temperature higher than the Setpoint temperature?

#H7

Is the boiler water temperature near or above 170F?

#H13

Meter the DHW circulator wires for 120Vac. Is there 120Vac available?

#H18

Check voltage on the Sage2 control on J4-2 to J4-12. Is 120Vac available?

#H25

Check voltage on the Sage2 control on J4-3 to J4-12. Is 120Vac available?

#H32

Check for 120Vac on the DHW terminals marked L & W. Is there 120Vac.

#H38

Is the boiler circulator running? This is the one back left inside the boiler jacket.

#P7

Touch the”Status” button. Using the left arrow key to the “Pump Status/Cycles” screen. Does this show the DHW circulator as “On”?

#P13

Using the “86” password check the “Pump Setup” menu. Is the DHW pump parameter set to “Primary Piped IWH”?

No
#P20

Change to “Primary Pipe IWH”. Did the problem resolve?

#P27

Replace wiring to the DHW circulator.

#P38

Touch the”Status” button. Using the left arrow key to the “Pump Status/Cycles” screen. Does this show the Boiler circulator as “On”?

#W7

Use the “X” in the upper right hand corner of the display go back to the Home Screen. Using the “Adjust ” button and the “86” password check the “Pump Setup” menu. Is the boiler pump parameter set to “Any Demand”?

#W13

Adjust the Boiler Pump parameter to “Any Demand”. Did this resolve the problem?

#W20

Check for 120Vac at the boiler circulator. The left side panel comes off the K2-WT for service to the circulator. Is there 120Vac available.

#AD7

Unplug the L1 harness. Test the boiler side of the plug for 120Vac. This is located near the circulator. Is 120Vac present?

#AD13

Replace the short harnes from there to the circulator.

#AD20

Replace the circulator.

#AK7

Measure 120Vac on the Sage2 control on J4-5 to J4-12. Is 120Vac available?

#AK13

Measure 120Vac on the Sag2 control on J4-4 to J4-12. Is 120Vac available?

#AK20

Measure voltage on the Line voltage PC board between P3-11 and the input “N” terminal on the PC board. Is 120Vac available?

#AK27

Measure voltage between the input terminals labeled L & N. Is 120Vac available?

Yes
#AK35

Replace Boiler Circulator harness

#AP21

Replace the Sage2.2 control

#AP25

Replace wire harness between Sage2 control and Line Voltage PC board.

#AP29

Replace the Line Voltage PC Board

#AP33