Soft Lockout 28 or 53: Interrupted Air Proving Switch Open

Condition

  • Air proving switch failed to close

Possible Cause

  • Check switch connections and wiring
  • Blocked Vent
    • Vent must always go uphill towards the termination
    • Listen to vent outside if possible for water noises
  • Blocked air inlet
  • Blocked or disconnected air proving switch tube
    • Remove tubing and blow through it
    • Inspect for kinks
    • Inspect for cracks/splitting in the tubing
  • Blocked heat exchanger
  • Blocked burner