Soft Lockout 2: Boiler Safety Limit Open

Condition

  • Boiler Safety Limit wired to terminals J6-1, 2 or 3 open
  • Thermal Fuse Switch contact open.
  • Air Pressure Switch contact open.
  • Auto Reset High Limit contact open.

More Info: Troubleshoot “Limit String”

Possible Cause

  • Loose wiring to limit device.
  • Auto Reset Supply high limit sensor detected temperature in excess of 200°F.
  • Defective Auto Reset Supply High Limit Switch.
  • Thermal Fuse Switch blown due to temperature rise above 358°F.
  • Air Pressure Switch contact open – check for blocked vent/air intake.
  • See possible causes for “Hard Lockout 4”.