TS-27: Sage Zone Control – Circulator Panel

Is the Sage Zone Control (SZC) used for circulators or zone valves?

#B7

Is the power light on?

#B13
TS Node Text
#TS Node

Meter voltage on L1 to L2. Is 120Vac available?

#B18

Return to the Main Menu and click on “Boiler Does Not Ignite or Lights and Goes Out Immediately”

#B24

Replace Sage Zone Control

#B30

Call tech services.

#B37

Is at least one of the 4 zone lights on?

#G7

Is the problem no heat from any zone or no heat from just one particular zone?

#G13

Determine why there is no voltage to L1 & L2 and make repairs. Caution: make sure the voltage to the Sage Zone Control is the same circuit the boiler is on.

#G18

Check 120Vac input voltage fuse #6 from left to right for continuity. Do you have continuity?

#G24

Turn up a thermostat or multiple thermostats.

OK
#M3

Verify there is a demand for heat on at least one zone. Is there a demand?

#M7

Is the zone light on for the problem zone?

#M13

Possible loss of communication between the SZC and the boiler. Press the status button, scroll to the right about 4 screens, do you see a screen that is headed with” Zone Control Status”. Is that display available?

#M20

Did a zone light come on?

#S7

Place a jumper between the thermostat connections for the zone terminals R & W. Did the light come on?

#S13

Possible defective cat-5 cable. If you have a new cat-5 cable replace the cable. If not you can wire the 3 envirocom terminals in the control to the boiler envirocom terminals on the Low Voltage Board on the boiler. Wire terminals 1-1, 2-2 and 3-3. Did the display show up in the Staut menu? It may take a minute or two.

#S20

Did the circulator start for that zone?

#X7

Replace SZC.

#X13

Cat-5 cable was bad. Problem is resolved.

#Z20

Press the status button on the display. About 3/4 of the way down on the display is Priority. It should display Central heat in a few seconds. The very bottom line should be sequencing through the start up process with a counter. When the boiler displays direct ignition the boiler should fire and then display running. Did the boiler turn on and fire?

#AD7

Zone panel is working as designed.

#AJ7

Using an electrical meter check voltage across the circulator terminals for the zone(s) not operating. You should read 110 – 130Vac. Do you have the proper voltage?

#AJ12

Did the Status screen Priority label show Central Heat or Domestic How Water if the demand Is on zone 4 and set to priority?

#AP7

Check Voltage at the appropriate circulator. Is there 120Vac at the circulator?

#AP12

Zone panel working correctly. If boiler does not light this is a boiler issue. Go to main menu and choose Boiler does not light or lights or lights and goes out immediately.

#AX7

Replace circulator

#AX12

Check or replace the wire from the zone panel to the circulator.

#BA12

Replace fuse.

#BC15

Remove the fuse for the appropriate zone(s). Check continuity through fuse. Does the fuse have continuity?

#AX15

Fuse Desginations

Fuses left to right:

  1. Primary Pump
  2. Zone circulator 1
  3. Zone circulator 2
  4. Zone circulator 3
  5. Zone circulator 4
  6. 120V input on L1 & L2
#BG7