TS-10: Boiler Does Not Ignite or Lights and Goes Out Immediately

Press the status button and view the bottom line. We energize the gas valve on “Direct Ignition” Does the gas valve open in “Direct Ignition” You can verify this by having a manometer on the inlet side of the gas valve and see if the gas pressure drops. Another way although not as good of a way is to hold the gas valve. If the pressure drops the valve is opening. Another way, although not as good of a way is to hold the gas valve and feel it opening.

#B4

Does the boiler light at all?

#B12

Remove the ignitor and inspect. Is the ignitor distorted or twisted.

#B15

Check the gap on the ignitor. Adjust to 0.16″ to 0.19″ (11/64″ +/- 1/64″) or 4 – 5mm. Adjust the ground rod, the one without the porcelain. Start boiler again, did the problem resolve?

#B20

Does the flame last at least 4 seconds?

#G12

Replace ignitor. Did the problem resolve?

#K15

Is this boiler fired on LP or natural gas?

#K20

With the manometer installed on the inlet side of the gas valve. When the valve opens does the gas pressure drop more than 1-1/2″ w.c.?

#K28

Check the regulator/meter and pipe sizing and length. If using CSST I suggest a minimum of 3/4″. Distance may require larger pipe.

#K37

When the control sparks does the ignitor spark? You should also hear the spark in the Sage control and at the igniter.

#P13

Install a manometer to the inlet pressure tap on the gas valve. Is the incoming gas pressure without the boiler running at or above 4.5″ w.c.?

#R20

Was the heat exchanger cleaned within the past 18 months?

#T28

Clean boiler heat exchanger and burner and try again. Did boiler light?

#T37

Did you hear the spark in the control during “pre-ignition” and “Direct ignition“? This would be an intermittent and continuous spark.

#V10

Replace the control

#V16

Replace the ignition cable

#Y16

Install a manometer to the inlet pressure tap on the gas valve. Is the incoming gas pressure without the boiler running at or above 11″ w.c. for Phantom.

#X20

Cover approximately 1/2 the opening of the air inlet of the fan shroud before the control goes to “Direct Ignition“. If the boiler lights on “direct ignition” keep your hand partially covering the opening for about 30 seconds. Does the boiler light?

#Y28

Open the “Modulation Setup” menu and try reducing the light-off rate to 3500 rpm’s. Did the boiler light?

#Y37

Turn the Throttle screw 1/2 turn counter-clockwise 1/2 turn. Did the boiler light?

#Y42

Replace Flame Sensor. A normal reading is 4 – 25 dependent on firing rate.

#W47

Keeping your hand on the air intake opening, check gas pressure. In high fire does pressure drop below the minimum on the rating plate?

#W52

Leave wire disconnected and protect the wire ends from touching any metal surfaces. Use electrical tape or cut ends off and wire nuts as protection. The lower small hole on the right side of the trap is an overflow. If you want to put a hose on the tapping and drain as a back-up drain. If water drains from the hose the primary drain requires cleaning.

#W58

Disconnect the ignition wire from the ignitor and control. Meter the ignition cable for ohms. Are the ohms above 1000 Ohms?

#AB11

Adjust the gas pressure to minimum gas pressures on the boiler label or higher not to exceed 14″ w.c. Normal natural gas pressures are 6″ w.c. to 8″ w.c. Lap normal gas pressures are 12.5″ w.c. to 13″ w.c.

#AD20

Does the boiler stay running when you remove your hand?

#AG28

Check the flame signal display. You will find this in the “Status” menu. Press status and scroll right until you see “Boiler status”. Doing start-up within about 4 seconds the flame Signal should be above 3 Micro-amps. Are Micro-amps high enough?

#AF39

Did the burner stay lit until the inducer fan ramped up to high fire and than go out?

#AF47

There is an orange wire between the Sage control and the condensate trap. The orange wire has a male & female spade connector about half way between the control and trap. Unplug the wires and fire the boiler. Did the boiler stay running?

#AF52

Disassemble the gas train and view/clean inducer fan blades and swirl plate. Are the swirl plate and/ or fan blades deteriorated?

#AF59

Connect your combustion analyzer to the vent connector by removing the test port cap. Lock the boiler in high fire and adjust the “02” and “CO” per the I&O manual. When complete turn boiler off and re-start.

See O2 Settings

#AL28

Turn the throttle screw another 1/2 turn counter-clockwise. Did the boiler light.

#AM40

Return the screw back 1 full turn clock-wise

#AN44

Inspect/clean the burner tube.

#AN48

Replace the deteriorated parts. Does the boiler light?

#AN52

Please contact Technical Support to resolve this issue.

#ZZ1

#B98

PHTNM Settings for Natural Gas

K2-FT O2 Settings for LP Gas

 

#X107

PHNTM Throttle screw adjustment from full closed Natural Gas

PHNTM Throttle screw adjustment from full closed LP Gas

 

#Y151

K2-WT Natural & LP

#X174

#AB209

#A207